1. **Problem Statement:**
We have two alternators A and B operating in parallel supplying a total load of 10,000 kW at 0.8 power factor lagging. Alternator A is adjusted to supply 6,000 kW at 0.92 lagging power factor. We need to find the power factor of alternator B.
2. **Given Data:**
- Total load power, $P_{total} = 10,000$ kW
- Total power factor, $\cos \phi = 0.8$ lagging
- Power factor angle, $\phi = \cos^{-1}(0.8) = 36.9^\circ$
- Alternator A power, $P_A = 6,000$ kW
- Alternator A power factor, $\cos \phi_A = 0.92$ lagging
- Alternator A power factor angle, $\phi_A = \cos^{-1}(0.92) = 23^\circ$
3. **Formulas and Important Rules:**
- Reactive power $Q = P \tan \phi$
- Total reactive power $Q_{total} = P_{total} \tan \phi$
- For lagging power factor, reactive power is positive (inductive load)
- Power supplied by B: $P_B = P_{total} - P_A$
- Reactive power supplied by B: $Q_B = Q_{total} - Q_A$
- Power factor of B: $\cos \phi_B = \frac{P_B}{\sqrt{P_B^2 + Q_B^2}}$
4. **Calculations:**
- Calculate total reactive power:
$$Q_{total} = 10,000 \times \tan 36.9^\circ = 10,000 \times 0.7508 = 7,508 \text{ kVAR}$$
- Calculate reactive power of A:
$$Q_A = 6,000 \times \tan 23^\circ = 6,000 \times 0.4245 = 2,547 \text{ kVAR}$$
- Calculate power of B:
$$P_B = 10,000 - 6,000 = 4,000 \text{ kW}$$
- Calculate reactive power of B:
$$Q_B = 7,508 - 2,547 = 4,961 \text{ kVAR}$$
- Calculate apparent power of B:
$$S_B = \sqrt{P_B^2 + Q_B^2} = \sqrt{4,000^2 + 4,961^2} = 6,373 \text{ kVA}$$
- Calculate power factor of B:
$$\cos \phi_B = \frac{P_B}{S_B} = \frac{4,000}{6,373} = 0.628$$
5. **Answer for (a):**
The power factor of alternator B is approximately **0.628 lagging**.
---
6. **Problem (b) Statement:**
If steam supply remains unchanged but excitation of B is reduced so that its power factor becomes 0.92 leading, find the new power factor of A.
7. **Given:**
- Power of B unchanged: $P_B = 4,000$ kW
- New power factor of B: $\cos \phi_B = 0.92$ leading
- $\phi_B = \cos^{-1}(0.92) = 23^\circ$
- Leading power factor means reactive power is negative (capacitive)
8. **Calculations:**
- New reactive power of B:
$$Q_B = 4,000 \times (-\tan 23^\circ) = 4,000 \times (-0.4245) = -1,698 \text{ kVAR}$$
- Total reactive power remains the same: $Q_{total} = 7,508$ kVAR lagging
- New reactive power of A:
$$Q_A = Q_{total} - Q_B = 7,508 - (-1,698) = 7,508 + 1,698 = 9,206 \text{ kVAR}$$
- Power of A unchanged: $P_A = 6,000$ kW
- Apparent power of A:
$$S_A = \sqrt{6,000^2 + 9,206^2} = 10,988 \text{ kVA}$$
- New power factor of A:
$$\cos \phi_A = \frac{6,000}{10,988} = 0.546$$
- Since reactive power is lagging, power factor is lagging.
9. **Answer for (b):**
The new power factor of alternator A is approximately **0.546 lagging**.
**Summary:**
- (a) Power factor of B = 0.628 lagging
- (b) New power factor of A = 0.546 lagging
Alternator Power Factor D103A0
Step-by-step solutions with LaTeX - clean, fast, and student-friendly.